Pathlight VX Site Preparation Guide 19
Verifying Power Connections and Rack Requirements
The Pathlight VX is a modular system that is mounted in a rack.
1
The Pathlight VX rack must meet the
following requirements.
Verify Power Cord
If the Pathlight VX is shipping in a rack, identify the power cord that will be used:
If the Pathlight VX is not shipping in a rack, identify the power cord that will be used:
1. Pathlight VX systems larger than the 35.9 TB High-Performance Configuration are installed in 2 adjacent racks.
Table 10 Power Cords for Pathlight VX Components for Racked Systems
ADIC Part
Number
Description
PVX Rack
Connection
Customer
Power
Connection
Cord
Length
(ft/m)
Cord
Gauge
Max Cord
Assembly
Rating
3-01505-04 North America L6-30 Socket L6-30 Plug 14/4.2 3 x 10AWG 240V/30A
3-01505-07 Europe/
International
L6-30 Socket 30/32A Cable
Mount Plug w/
PVX Sleeve
14/4.2 3 x 12AWG 250V/30A
3-01505-06 Australia L6-30 Socket 3 Round Pins.
Industrial Angle
Plug - IP66
14/4.2 3 x 12AWG 250V/30A
Table 11 Power Cords for Pathlight VX Components for Non-racked Systems
ADIC Part
Number
Description
Component
Connection
Customer
Power
Connection
Cord
Length
(ft/m)
Cord
Gauge
Max Cord
Assembly
Rating
1-01013-01 UK C13 BS1363 8.2/2.5 3 x 16AWG 250V/10A
1-01033-01 Europe C13 CEE 7/VII 8.2/2.5 3 x 16AWG 250V/10A
1-01034-01 North America C13 N5/15 7.5/2.3 3 x 18AWG 125V/10A
Note
Power cords for DPEs and DAEs are ordered as separate items only for non-
racked systems. In racked systems, the power cords for DPEs and DAEs are
included in the BOM.
To review the number of power cords required for each configuration, see
Table 12
on page 21. You can also use the Configurator tool during order entry
to determine the number of power cords required.