Chapter 8: Installing, Removing, and Replacing Components
Removing and Replacing the System Control Board
230 Quantum Scalar i40 and Scalar i80 User’s Guide
5 Access the Web client using the IP address and log in using the
default user name and password:
• User name: admin
• Password: password
6 Optionally, install tape drive firmware for autoleveling. The library
firmware contains baseline tape drive firmware for autoleveling.
Verify your tape drive firmware is at the level you expect. If not:
a Upload the tape drive firmware you want to use. From the Web
client, select Tools > Drive Operations > Upload/remove tape
drive firmware for autoleveling.
b Unload all tape cartridges from the tape drives on which you
want to autolevel firmware.
c Initiate autoleveling by doing one of the following:
• Restart the library (from the operator panel, select Actions
> Shutdown > Restart Library.
• Restart all the tape drives you want to autolevel, as follows:
From the Web client, select Tools > Diagnostics. Confirm
you want to take the partitions offline. Select Drives >
Drive Tests > Drive Reset. Select the applicable partitions
and tape drives, then click Apply, then click OK.
7 If you changed the IP address from what it was originally, update
host and other applications that access the library.
8 Update the library name, time zone, and any other configuration
settings, if required, using the Web client Setup menus.
9 Save the library configuration. From the Web client, select Tool s >
Save/Restore Configuration. Select Save Configuration and click
Apply. Save the configuration to a known location.
10 It is recommended that you run the Installation and Verification Test
(IVT). From the operator panel, select To ol s > IV T and follow the
instructions. The IVT takes about 30 minutes. If any problems are
detected, the library issues a diagnostic ticket.
11 Package the old SCB in the packaging that shipped with the new
SCB and send the old SCB back to Quantum.