Scalar 100 User’s Guide 31
Removing the Standard Mailbox
Use Figure 10 to assist you in removing the standard mailbox.
Figure 10 Removing a Standard Mailbox
1 Turn off the Scalar 100 library. (Both the front and the rear power switches.)
2 Open the library front door. Remove the tape cartridge(s) from the standard mailbox.
3 Remove the three mailbox cable clamps. Two of the cable clamps are attached to the door with #2
Phillips screws and one is attached with a 11/32 nut. Disconnect the mailbox cable harness from the
display assembly.
4 Remove the five 11/32 nuts that attach the mailbox assembly to the front door. There are two nuts on
the left side and three on the right side.
11/32 Nuts
(Left Side)
Single Slot Mailbox
Mailbox cable harness
Connector to
Display Assembly
Display Assembly
Cable Clamps
T20 Torx Screw